![]() Hi,
After reading all the posts on this forum I am fairly certain we will be using synthetic standing rigging. We will have a gaff rig, and I'm wondering if anybody has any previous experience on providing lightning protection for a rig with a wood mast and synthetic shrouds. I'm going to be laminating up our spars next month and at the moment planning to run a large conductor internally and bond it to underwater metal. I am somewhat concerned about heating of this conductor and it will be over sized from the nominal NFPA/AYBC 4awg guidance. Thoughts ? Comments ? Hoping somebody else has thought about this also. Cheers, Mark |
#2
|
|||
|
|||
![]() This topic has been flogged to death on other forums without a conclusive answer--it seems we still know less about lightning than we'd like. I fall into the camp of: "why offer lightning a path to ground?" and thus my aluminum mast is not grounded to anything--it just ends at it's tabernacle on deck. The synthetic shrouds also don't offer a path, and since they're non-absorbent, there would only be surface water to act as a conductor.
So far we haven't been struck, but I attribute that more to Providence than to having done the right thing. Since I'm still not sure what the right thing is. Good luck. Ben |
![]() |